Figure 41 - Mounting Orientation A
(Standard Orientation)
Figure 42 - Mounting Orientation B
(Upside Down)
Figure 43 - Mounting Orientation C
(Table-top Mounting))
Figure 44 - Mounting Orientation D
(Horizontal Input on the Left)
Figure 45 - Mounting Orientation E
(Horizontal Input on the Right)

Mounting Orientations

Mounting orientations other than all terminals on the bottom require a
reduction in continuous output power or a limitation in the maximum allowed
ambient temperature. The amount of reduction influences the lifetime
expectancy of the power supply. Therefore, two different derating curves for
continuous operation can be found below:
Curve A1: Recommended output current.
Curve A2: Max allowed output current (results in approximately half the
lifetime expectancy of A1).
OUTPUT
Power
Supply
INPUT
Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
Output Current
12A
9
6
3
Ambient Temperature
0
10
20
30
40
Output Current
12A
9
6
3
Ambient Temperature
0
10
20
30
40
Output Current
12A
9
6
3
Ambient Temperature
0
10
20
30
40
Output Current
12A
9
6
3
Ambient Temperature
0
10
20
30
40
Output Current
12A
9
6
3
Ambient Temperature
0
10
20
30
40
50
60°C
50
60°C
50
60°C
50
60°C
50
60°C
33