Dielectric Strength - Allen-Bradley 1606-XLE240ERL Reference Manual

Redundancy power supply - 24v, 10 a, 240 w, single-phase input
Table of Contents

Advertisement

Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
D
S
ielectric
trength
22
The output voltage is floating and has no ohmic connection to the ground.
Type and routine tests are conducted by the manufacturer. Field tests may be
conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2 s up and 2 s down). Connect all input-terminals
together as well as all output poles before conducting the test. When testing,
set the cut-off current settings to the value in the table below.
Type test
Routine test
Field test
Cut-off current setting for field test > 10 mA
It is recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the
earth/ground system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off
when unnoticed earth faults occur.
(1) When testing input to DC OK ensure that the maximal voltage between DC OK and the output is not exceeded (column D). We
recommend connecting DC OK pins and the output pins together when performing the test.
Figure 25 - Dielectric Strength
Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
A
B
60s 2,500V AC
4,000V AC
5s
2,500V AC
2,500V AC
5s
2,000V AC
2,000V AC
> 10 mA
Input
DC-ok
B (1)
L
N
A
Output
Earth, PE
C
(1)
C
D
1,000V AC
500V AC
500V AC
500V AC
500V AC
500V AC
> 20 mA
> 1 mA
D
+
-