Advertisement

Kinetix 5700 Regenerative Bus Supply
Minimum Clearance Requirements
Kinetix 5700
Regenerative Bus Supply
Clearance left of the
module is not required.
Refer to
Product Dimensions
for regenerative bus supply dimensions.
IMPORTANT
The Kinetix 5700 drive system must be spaced by aligning the zero-stack tab and cutout. To
mount, size, and configure shared-bus configurations, refer to the Kinetix 5700 Servo Drives
User Manual, publication 2198-UM002.
Zero-stack Tab and
Cutout Aligned
Mount the Kinetix 5700 regenerative bus supply to the cabinet subpanel with M5 (#10-32) steel
bolts torqued to 4.0 N•m (35.4 lb•in), max.

Mounting Hole Patterns

This section provides mounting hole patterns for Kinetix 5700 regenerative bus supplies that are
mounted in zero-stack (shared-bus) configurations. The regenerative bus supply can be mounted
on the far right, far left, or anywhere in between. However, the far left position is preferred to
accommodate the 24V shared bus.
8
For Airflow and Installation
MOD
NET
2
1
I/O
1
6
10
5
on
page 10
Clearance Below
For Airflow and Installation
Mount the regenerative bus supply in an upright position as shown. Do not mount the unit on
its side.
Rockwell Automation Publication 2198-IN014A-EN-P - August 2018
Clearance Above
Clearance right of the
module is not required.
OK+
OK–
EN–
EN+
Bus Supply
Cat. No.
2198-RP088
2198-RP200
2198-RP263
2198-RP312
MOD
NET
Clearance
Clearance
Above
Below
mm (in.)
mm (in.)
100 (3.94)
40 (1.57)
150 (5.91)
80 (3.15)
200 (7.87)
Shared-bus connection
system is not shown
for clarity.
MOD
MOD
NET
NET