Group 2 Digital Input/Output Parameters
02-00
2-wire/3-wire Operation Control
Control
VF
VFPG
mode
Settings
Three of the six methods include a "Line Start Lockout" feature. When line start lockout is
enabled, the drive will not run once applying the power. The Line Start Lockout feature doesn't
guarantee the motor will never start under this condition. It is possible the motor may be set in
motion by a malfunctioning switch.
This parameter is used to control operation from external terminals. There are three different
control modes.
2-wire operation control (1)
FWD/STOP
REV/STOP
2-wire operation control (2)
RUN/STOP
REV/FWD
3-wire operation control
Multi-Function Input Command 1 (MI1)
02-01
(it is Stop terminal for 3-wire operation)
Revision Nov. 2008, VLE1, SW V1.03
SVC
FOCPG TQCPG FOCPM
0
FWD/STOP, REV/STOP
1
FWD/STOP, REV/STOP (Line Start Lockout)
2
RUN/STOP, REV/FWD
3
RUN/STOP, REV/FWD (Line Start Lockout)
4
3-wire
5
3-wire (Line Start Lockout)
02-00
0, 1
FWD/STOP
REV/STOP
2, 3
RUN/STOP
FWD/REV
4, 5
Control Circuits of the External Terminal
DCM
DCM
FWD "CLOSE":RUN
RUN
STOP
MI1 "OPEN":STOP
REV/FWD "OPEN": FWD
REV/FWD
DCM
Chapter 4 Parameters|
Factory setting: 0
FWD:("OPEN":STOP)
("CLOSE":FWD)
REV:("OPEN": STOP)
("CLOSE": REV)
VFD-VL
FWD:("OPEN":STOP)
("CLOSE":RUN)
REV:("OPEN": FWD)
("CLOSE": REV)
VFD-VL
"CLOSE": REV
VFD-VL
Factory Setting: 1
4-37