Delta Electronics Elevator Drive VFD-VL User Manual page 86

Elevator drive
Table of Contents

Advertisement

1st Output
Voltage Setting 1
2nd Output
Voltage Setting 1
3rd Output
Voltage Setting 1
4th Output
Voltage Setting 1
01-09
Start Frequency
Control
VF
VFPG
mode
Settings
To distinguish which frequency should be start frequency, it needs to compare the value of min.
output frequency and start frequency. The larger value will be start frequency.
When min. output frequency > start frequency
min. output
frequency
start frequency
01-10
Output Frequency Upper Limit
Control
VF
VFPG
mode
Settings
01-11
Output Frequency Lower Limit
Control
VF
VFPG
mode
Settings
The upper/lower output frequency setting is used to limit the actual output frequency. If the
frequency setting is lower than the start-up frequency, it will run with zero speed. If the
frequency setting is higher than the upper limit, it will runs with the upper limit frequency. If
output frequency lower limit > output frequency upper limit, this function is invalid.
Revision Nov. 2008, VLE1, SW V1.03
Voltage
Output Frequency
01-11
Lower Limit
01-02
Frequency output
ranges limitation
01-04
01-06
01-08
01-07
01-09
3rd Freq.
4th Freq.
Start Freq.
V/f Curve
SVC
FOCPG
0.00~120.00Hz
SVC
FOCPG FOCPM
0.00~120.00Hz
SVC
FOCPG FOCPM
0.00~120.00Hz
Output Frequency
Upper Limit
01-10
01-05
01-03
01-01
1st Freq.
2nd Freq.
When start frequency > min. output frequency
start frequency
min. output
frequency
Chapter 4 Parameters|
Regular V/f Curve
Special V/f Curve
Frequency
01-00
Maximum Output
Frequency
Factory setting: 0.50
Factory setting: 120.00
Factory setting: 0.00
Unit: 0.01
Unit: 0.01
Unit: 0.01
4-31

Hide quick links:

Advertisement

Table of Contents
loading