Delta Electronics Elevator Drive VFD-VL User Manual page 134

Elevator drive
Table of Contents

Advertisement

07-19
Source of Torque Offset
Control
SVC
FOCPG TQCPG FOCPM
mode
Settings
This parameter is the source of torque offset.
When it is set to 3, the source of torque offset will decide to Pr.07-21, Pr.07-22 and Pr.07-23
by the multi-function input terminals setting (19, 20 or 21).
02-01~02-08 is set to 19 02-01~02-08 is set to 20 02-01~02-08 is set to 21
OFF
OFF
OFF
OFF
ON
ON
ON
ON
07-20
Torque Offset Setting
Control
SVC
FOCPG TQCPG FOCPM
mode
Settings
This parameter is torque offset. The motor rated torque is 100%.
07-21
High Torque Offset
Control
SVC
FOCPG TQCPG FOCPM
mode
Settings
07-22
Middle Torque Offset
Control
SVC
FOCPG TQCPG FOCPM
mode
Settings
Revision Nov. 2008, VLE1, SW V1.03
0
Disable
1
Analog input (Pr.03-00)
2
Torque offset setting (Pr.07-20)
3
Control by external terminal (by Pr.07-21 to Pr.07-23)
OFF
OFF
ON
ON
OFF
OFF
ON
ON
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
Chapter 4 Parameters|
OFF
ON
OFF
ON
OFF
ON
OFF
ON
07-23+07-24+07-25
Factory Setting: 0.0
Factory Setting: 30.0
Factory Setting: 20.0
Factory Setting: 0
Torque offset
None
07-25
07-24
07-25+07-24
07-23
07-23+07-25
07-23+07-24
Unit: 0.1
Unit: 0.1
Unit: 0.1
4-79