Delta Electronics Elevator Drive VFD-VL User Manual page 126

Elevator drive
Table of Contents

Advertisement

06-22
Fault Output Option 1
06-23
Fault Output Option 2
06-24
Fault Output Option 3
06-25
Fault Output Option 4
Control
VF
VFPG
mode
Settings
These parameters can be used with multi-function output (set Pr.02-11 to Pr.02-22 to 35-38)
for the specific requirement. When the fault occurs, the corresponding terminals will be
activated (It needs to convert binary value to decimal value to fill in Pr.06-22 to Pr.06-25).
Fault code
0: No fault
1: Over-current during acceleration
(ocA)
2: Over-current during deceleration
(ocd)
3: Over-current during constant speed
(ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-curent at stop (ocS)
7: Over-voltage during acceleration
(ovA)
8: Over-voltage during deceleration
(ovd)
9: Over-voltage during constant speed
(ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration
(LvA)
12: Low-voltage during deceleration
(Lvd)
13: Low-voltage during constant
speed (Lvn)
14: Low-voltage at stop (LvS)
Revision Nov. 2008, VLE1, SW V1.03
SVC
FOCPG TQCPG FOCPM
0 to 65535 sec (refer to bit table for fault code)
Bit0
current Volt.
Bit1
Bit2
OL
Chapter 4 Parameters|
Factory setting: 0
Bit3
Bit4
Bit5
SYS
FBK
EXI
Unit: 1
Unit: 1
Unit: 1
Unit: 1
Bit6
CE
4-71