The COMMREQ function block parameters are described in the table below. Set values for
these parameters as required by the application.
Parameter
IN
SYSID
TASK
FT
ENO
5.11

Program Download

After parameters in the ST block have been set up as required by the application, the project
can be downloaded to the RX3i controller for verification and operation.
5.12

IEC 104 Communications Start-up

The EIS001 module will power up and signal the user program through LIS bit 11 that it is
ready to receive the configuration parameters as defined in the ST block. LIS bit 11 and LIS
bit 13 (LAN OK) are used together in the user program to execute the one-shot signal to
configure the module with its parameters.
LAN Interface Status (LIS) bits 10, 11, and 12 are reserved for use with Ethernet applications.
Only LIS bit 11 is used with the IEC 104 Server; reference the status information below for
operational details.
LIS bit 11
0
1
5.13

COMMREQ Status Word Codes

After power-up of the RX3i controller, the status of the IEC 104 Server can be checked in the
COMMREQ Status Word. Refer to the table below for status code values and descriptions.
Status Code
1
40592
Configuration of IEC-104 Server Parameter
Value
Description
mComreq_Setup
Location of the COMMREQ Command Block Parameters,
always mComreq_Setup
iRackSlot
Slot Location of the IEC 104 EIS001 module in RX3i
Rack, always iRackSlot
0
Task Value,
always 0
mComreq_CallSta
Fault Output,
always mComreq_CallSta
mComreq_ENO
Enable Output,
always mComreq_ENO
Description
IEC 104 Server is not executing.
IEC 104 Server is executing and is ready for configuration.
Description
Successful configuration of the IEC 104 Server.
Warning: The IEC 104 Server is already configured and
operating.