Parameters For Filter Times; Parameters For Short And Long Pulse Durations - Emerson PACSystems RX3i User Manual

Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User Manual
GFK-2949E
5.8.1

Parameters for Filter Times

Parameter
mComreq_Setup [11]
mComreq_Setup [12]
Note:
5.8.2

Parameters for Short and Long Pulse Durations

Parameter
mComreq_Setup [13]
mComreq_Setup [14]
Configuration of IEC-104 Server Parameter
Value
0 to 65530
0 to 65530
There is no interlock between the filter times.
Value
0 to 65530
0 to 65530
Description
Input Change Filter Time, default is 10 ms, typical [3x
Controller Sweep]. The Input Change Filter is a shutter on
the data intake by the module from the Controller.
If value configured is less than 10, then the value is
internally clamped to 10 ms by the EIS001 firmware.
If value configured is greater than 65530, then the value
is internally clamped to 65530 ms by the EIS001
firmware.
Report by Exception Shutter Time, default is 25ms.
The RBE filter time is not a holding time. It is a general
shutter to control the flow of data back to the Client.
If value configured is less than 25, then the value is
internally clamped to 25 ms by the EIS001 firmware.
If value configured is greater than 65530, then the value
is internally clamped to 65530 ms by the EIS001
firmware.
Description
Short Pulse Duration, default 250 ms
Valid range 10 to 65530 ms.
If value configured is less than 10, then the value is
internally clamped to 150 ms by the EIS001 firmware.
If value configured is greater than 65530, then the
value is internally clamped to 65530 ms by the EIS001
firmware.
Long Pulse Duration, default 500ms
Valid range 10 to 65530 ms.
If value configured is less than 10, then the value is
internally clamped to 500 ms by the EIS001 firmware.
If value configured is greater than 65530, then the
value is internally clamped to 65530 ms by the EIS001
firmware.