Memory Translation Feature Configuration Parameters; Parameters For Read Translation Table - Emerson PACSystems RX3i User Manual

Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User Manual
GFK-2949E
Parameter
mComreq_Setup [10]
5.7
Memory Translation Feature Configuration
Parameters
The Optional Configuration Parameters listed in Section 5.8 are optional for RX3i IEC 104
Server configuration files. The Memory Translation feature can be configured using the
parameters as described in this section.
All configuration parameter values should be entered in decimal format. Refer to the
parameter description to determine valid input values for application-based, or user-
defined, parameter settings.
Note:
Unambiguous Addressing Scheme for Legacy 104 SCADA Clients
The addressing scheme for EIS001 release 1.00 supports ambiguous addressing, i.e. offset-
based addressing for ADSUs. Some legacy SCADA clients (like CPELE/SAGE) may require
unambiguous addressing (Unique addressing) for each ADSU object. The Memory
Translation Feature Configuration Parameters support unambiguous Object Addressing.
5.7.1

Parameters for Read Translation Table

Parameter
mComreq_Setup [75]
mComreq_Setup [76]
mComreq_Setup [77]
mComreq_Setup [78]
mComreq_Setup [79]
mComreq_Setup [80]
mComreq_Setup [81]
mComreq_Setup [82]
mComreq_Setup [83]
Configuration of IEC-104 Server Parameter
Value
1
Reserved parameters always have a value of zero (0).
Description
Number of Segments
Value: 1
Value
Description
0 to 32000
Read Translation Table MSP
0 to 32000
Read Translation Table MDP
0 to 32000
Read Translation Table MST
0 to 32000
Read Translation Table MBO
0 to 32000
Read Translation Table MMENA
0 to 32000
Read Translation Table MMENB
0 to 32000
Read Translation Table MMENC
0 to 32000
Read Translation Table MEPTB
0 to 32000
Read Translation Table MEPTC
Chapter 5
Dec 2020
34