GFK-2949E
MEPTB Configuration
*Future M_EP_TB ADSU COMMREQ Configuration does not scan the Controller memory,
you must use Point Push interface for this ADSU.
Parameter
mComreq_Setup [46]
mComreq_Setup [47]
mComreq_Setup [48]
mComreq_Setup [49]
MEPTC Configuration
*Future M_EP_TC ADSU COMMREQ Configuration does not scan the Controller memory,
you must use Point Push interface for this ADSU.
Parameter
mComreq_Setup [50]
mComreq_Setup [51]
mComreq_Setup [52]
mComreq_Setup [53]
5.8.5

Option Parameters

Parameter
mComreq_Setup [66]
mComreq_Setup [67]
Configuration of IEC-104 Server Parameter
Value
Description
m-type value
unused
address value
unused
Length
unused
CPO
unused
Value
Description
m-type value
unused
address value
unused
Length
unused
CPO
unused
Value
Description
0 / 1
Bit 1 – Clock Validity lasts for 1 hour
Bit 2 – Clock Validity lasts for 24 hours
*Note if Bit 1 and 2 are OFF, clock is valid forever; this is
used when there is a time synch to the Controller such as
IRIG-B.
Bit 3 – Do Not accept time synch from a client
Bit 4 - 1 : CPU Time is taken for Event Time tagging
0 : EIS001 Module Time is taken for Event Time
tagging
Bit 5 & Bit 6 – Multiple Client Connection Configuration
0 / 1
Bit 1 – When 1 SOE Disabled for M_SP
Bit 2 – When 1 SOE Disabled for M_DP
Bit 3 – When 1 SOE Disabled for M_ST
Bit 4 – When 1 SOE Disabled for M_BO
Bit 5 – When 1 SOE Disabled for M_ME_NA