Mitsubishi Electric MELSERVO-J3 Series Instruction Manual page 149

Hide thumbs Also See for MELSERVO-J3 Series:
Table of Contents

Advertisement

APPENDIX
(6) Options, peripheral devices
Use the UL/C-UL Standard-compliant products.
Use the no-fuse breaker (UL489 Listed MCCB) or a Class T fuse indicated in the table below.
Servo amplifier
MR-J3-10B(1)-RJ006 20B-RJ006
MR-J3-40B-RJ006 20B1-RJ006
MR-J3-60B-RJ006 to 100B-RJ006
40B1-RJ006
MR-J3-200B-RJ006
MR-J3-350B-RJ006
MR-J3-500B-RJ006
MR-J3-700B-RJ006
MR-J3-11KB-RJ006
MR-J3-15KB-RJ006
MR-J3-22KB-RJ006
MR-J3-60B4-RJ006
MR-J3-100B4-RJ006
MR-J3-200B4-RJ006
MR-J3-350B4-RJ006
MR-J3-500B4-RJ006
MR-J3-700B4-RJ006
MR-J3-11KB4-RJ006
MR-J3-15KB4-RJ006
MR-J3-22KB4-RJ006
Note. Listed no-fuse breakers are for when the power factor improving reactor is not used.
(7) Capacitor discharge time
The capacitor discharge time is as follows. To ensure safety, do not touch the charging section for 15
minutes after power-off.
Servo amplifier
MR-J3-10B-RJ006 20B-RJ006
MR-J3-40B-RJ006 60B(4)-RJ006
10B1-RJ006 20B1-RJ006
MR-J3-70B-RJ006
MR-J3-40B1-RJ006
MR-J3-100B(4)-RJ006
No-fuse breaker (Note)
Current
30A frame 5A
30A frame 10A
30A frame 15A
30A frame 20A
30A frame 30A
50A frame 50A
100A frame 75A
100A frame 100A
225A frame 125A
225A frame 175A
30A frame 5A
30A frame 10A
30A frame 15A
30A frame 20A
30A frame 30A
50A frame 40A
60A frame 60A
100A frame 75A
225A frame 125A
Discharge
time (min)
1
2
3
4
5
App. - 12
Voltage AC
Current
10A
15A
20A
40A
240V
70A
125A
150A
200A
250A
350A
10A
15A
25A
35A
600Y/347V
50A
65A
100A
150A
175A
Servo amplifier
MR-J3-200B(4)-RJ006 350B-RJ006
MR-J3-350B4-RJ006 500B(4)-RJ006
700B(4)-RJ006
MR-J3-11KB(4)-RJ006
MR-J3-15KB(4)-RJ006
MR-J3-22KB(4)-RJ006
Fuse
Voltage AC
300V
600V
Discharge
time (min)
9
10
4
6
8