Option Fault Monitors U6-98 And U6-99 - YASKAWA PROFINET SI-EP3 Installation Manual

Hide thumbs Also See for PROFINET SI-EP3:
Table of Contents

Advertisement

Code
Name
oFA30 to
Option Card
oFA43
Connection Error
(CN5-A)
Option Not
oFb00
Compatible with Port
oFb02
Option Fault
oFC00
Option Fault (CN5-B)
oFC02
Option Fault

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive
keypad as shown in
Fault Condition
No Fault
Force Fault
Network Link Down
Network Failure
Default MAC
Address
No IP Address
YASKAWA TOEP C730600 89B PROFINET Installation Manual
Causes
A fault occurred in the option.
The option connected to
connector CN5-B is not
compatible.
An option of the same type is
already installed in option port
CN5-A, CN5-B, or CN5-C.
The option connected to
connector CN5-C is not
compatible.
An option of the same type is
already installed in option port
CN5-A, CN5-B, or CN5-C.
Table
9.1.
Table 9.1 Option Fault Monitor Descriptions
Status
Fault
Value
Declared
(U6-98/
U6-99)
N/A
0
EF0
3
bUS
1300
bUS
1301
None
1303
None
1304
1.
2.
3.
Connect the option to the correct
connector.
• Use connector CN5-A when you
connect the option.
To use other options, refer to those
option manuals.
Connect the option to the correct option
port.
Connect the option to the correct
connector.
• Use connector CN5-A when you
connect the option.
To use other options, refer to those
option manuals.
Connect the option to the correct option
port.
Description
No Fault
Network sent a message to force this node to the fault state.
No network link to option board.
Connection with PLC Timeout.
Factory default MAC Address programmed into the option.
Return for reprogramming.
No IP Address has been programmed into the option.
9 Troubleshooting
Possible Solutions
De-energize the drive.
Make sure that the option is
correctly connected to the connector.
If the problem continues, replace the
option.