Levelflex FMP53 HART
Start device check
Navigation
Description
Selection
Factory setting
Additional information
Result device check
Navigation
Description
Additional information
Last check time
Navigation
Description
Endress+Hauser
16.4.7
"Device check" submenu
Navigation
Diagnostics → Device check
Diagnostics → Device check → Start device check
Start a device check.
• No
• Yes
No
In the case of a lost echo a device check can not be performed.
Diagnostics → Device check → Result device check
Displays the result of the device check.
Meaning of the display options
• Installation ok
Measurement possible without restrictions.
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the
signal amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check
the mounting position of the device and the dielectric constant of the medium.
• Check not done
No device check has been performed.
Diagnostics → Device check → Last check time
Displays the operating time at which the last device check has been performed.
Operating menu
189