Operating menu
Switch-off delay
Navigation
Prerequisite
Description
User entry
Factory setting
Failure mode
Navigation
Prerequisite
Description
Selection
Factory setting
Additional information
Switch status
Navigation
Description
Invert output signal
Navigation
Description
Selection
158
Setup → Advanced setup → Switch output → Switch-off delay
• Switch output function (→ 154) = Limit
• Assign limit (→ 155) ≠ Off
Defines the delay applied before the output is switched off.
0.0 to 100.0 s
0.0 s
Setup → Advanced setup → Switch output → Failure mode
Switch output function (→ 154) = Limit or Digital Output
Defines the state of the switch output in case of an error.
• Actual status
• Open
• Closed
Open
Setup → Advanced setup → Switch output → Switch status
Current status of the switch output.
Setup → Advanced setup → Switch output → Invert output signal
' N o' The switch output behaves as per its parameter setting. ' Y es' The switching behavior is
inverted as compared to its parameter setting.
• No
• Yes
Levelflex FMP53 HART
Endress+Hauser