ECO functions

Summer/winter heating
limit
78/221
Siemens Switzerland Ltd
HVAC Products
To assure this function, following must be observed:
A room sensor must be connected
The "Room influence" setting must be between 1 and 99
There should be no thermostatic radiator valves in the reference room (mounting
location of room sensor) (If such valves are present, they must be set to their fully
open position).
Line no.
HC1
HC2
HC3P
730
1030 1330
732
1032 1332
The summer / winter heating limit is used to switch the heating on and off in the course
of the year, depending on temperature conditions. In Automatic mode, switching on / off
takes place automatically, so there is no need for the user to do this manually. By
changing the setting, the respective periods of time will be shortened or extended.
Increase:
Winter operation will start earlier
Summer operation will start later
Decrease:
Winter operation will start later
Summer operation will start earlier
• The function is not active in operating mode "Continuously nominal temperature"
• The display will show ECO
• To give consideration to the building's thermal dynamics, the outside temperature is
attenuated
Example:
T
°C
20
19
18
17
16
ON
OFF
0
5
SWHG Summer/winter heating limit
TAged Attenuated outside temperature
T
Temperature
t
Days
User manual RVS61.843
6 The settings in detail
Operating line
Summer/winter heating limit
24-hour heating limit
TAged
SWHG +1 °C
SWHG
SWHG -1 °C
t
10
15
CE1U2355en_02
23. November 2007