Danfoss FC Drive Terminal Configurations & Functions 
Type 
LINE 
POWER 
MOTOR 
TERMINALS 
DC BUS 
DIGITAL INPUTS 
DIGITAL IN OR OUT 
CONTROL 
DIGITAL INPUT 
TERMINALS 
ANALOG INPUTS 
ANALOG OUTPUT 
24VDC SUPPLY 
CONTROL POWER 
10VDC SUPPLY 
SUPPLY 
TERMINALS 
COMMON 
RELAY 1 
RELAY TERMINALS 
RELAY 2 
COMMUNICATION 
RS‐485 SERIAL 
TERMINALS 
COMMUNICATION 
Programming for Digital & Analog Inputs/Outputs  (P 0‐03 North American Default) 
Terminal 
Function 
18 
[8] START
19 
[0] NO OPERATION
27 
[7] EXTERNAL INTERLOCK
29 
[14] JOG
32 
[0] NO OPERATION
33 
[0] NO OPERATION
37 
[1] SAFE STOP ALARM
42 
[137] SPEED 4‐20mA
53 
REF RESOURCE 1 
54 
FEEDBACK 
Function 
Terminal # 
91, 92, 93 
96, 97, 98 
88, 89 
18, 19, 32, 33 
27, 29 
37 
53, 54 
42 
12, 13 
50 
20 
39 
55 
61 
68 
69 
Type 
Parameter 
P 5‐10 
D IN 
P 5‐11 
D IN 
P 5‐12 
D IN 
P 5‐13 
D IN 
P 5‐14 
D IN 
P 5‐15 
D IN 
P 5‐19 
D IN 
P 6‐50 
A OUT 
P 6‐1* 
A IN 
P 6‐2* 
A IN 
Label 
L1, L2, L3 
3‐Phase Power Input 
U, V, W 
3‐Phase Motor Output 
DC‐, DC+ 
DC Bus Connections 
D IN 
Digital Input (0V or 24VDC) 
D IN/OUT 
Configurable for Digital Input or Output (0V or 24VDC) 
D IN 
Safe Torque Off (STO) (optional) 
A IN 
0 to +10VDC or 0/4mA to 20mA 
A OUT 
0/4mA to 20mA 
+24V OUT
24VDC Power Supply (200mA maximum) 
+10V OUT
10VDC Power Supply (15mA maximum) 
COM D IN 
Power Supply Common (0V)  
COM A OUT 
(All COMMON supply terminals connected internally) 
COM A IN 
COM 
Common 
NO 
Normally Open Contact 
NC 
Normally Closed Contact 
COM 
Common 
NO 
Normally Open Contact 
NC 
Normally Closed Contact 
COM RS‐485 
Signal Common 
P RS‐485 
RS‐485 Interface; Note: Control card switch provided 
N RS‐485 
for termination resistance 
Description / Notes 
24VDC input will initiate a START command 
No functionality assigned 
Removing 24VDC will initiate a COAST function and generate an Alarm 60. 
International default is Coast Inverse which will not generate a fault when open.
24VDC input will initiate a JOG command; 
No functionality assigned 
No functionality assigned 
Safe Torque Off (STO) (Optional) 
4 to 20mA; 4mA @ 0‐speed, 20mA @ high‐speed limit (P 4‐13 or P 4‐14) 
Speed reference input 
Process closed loop feedback signal 
8
Notes 
Jog speed set via P 3‐10 or P 3‐11.
Voltage or current signal type 
determined by DIP switch 
selection under LCP (U‐I)  
 
 