GROUP 3 – Third (right) word: Operation Status 
Operation status              
AC brake was selected in parameter 2‐10 Brake Function. The AC brake over‐magnetizes the 
AC brake 
motor to achieve a controlled slow down. 
AMA finish OK 
Automatic motor adaptation (AMA) was carried out successfully. 
AMA ready 
AMA is ready to start. To start, press Hand On. 
AMA running 
AMA process is in progress. 
Braking 
The brake chopper is in operation. The brake resistor absorbs the generative energy. 
The brake chopper is in operation. The power limit for the brake resistor defined in 
Braking max. 
parameter 2‐12 Brake Power Limit (kW) has been reached. 
PROFIDrive profile was selected in par. 8‐10 Control Word Profile. Via serial communication 
Bus Jog 1 
the Jog 1 function is activated. The Motor is running with par. 8‐90 Bus Jog 1 Speed. 
PROFIDrive profile was selected in par. 8‐10 Control Word Profile. Via serial communication 
Bus Jog 2 
the Jog 2 function is activated. The Motor is running with par. 8‐91 Bus Jog 2 Speed. 
The output frequency is corrected by the value set in par. 3‐12 Catch up/slow Down Value. 
1. Catch up is selected as a function for a digital input (parameter group 5‐1* Digital Inputs). 
Catch up 
The corresponding terminal is active. 
2. Catch up was activated via serial communication. 
• 2 Coast inverse was selected as a function for a digital input (parameter group 5–1* Digital 
Coast 
Inputs). The corresponding terminal is not connected. 
• Coast activated by serial communication. 
PROFIDrive profile was selected in par. 8‐10 Control Word Profile. The FC needs the second 
Control ready 
part of the two‐part serial start command (e.g. 0x047F) via serial communication to allow 
starting. Using an input terminal is not possible. 
1 Ctrl. ramp‐down was selected in parameter 14‐10 Mains Failure. 
Ctrl. ramp‐
• Mains voltage is below the value set in parameter 14‐11 Mains Voltage at Mains Fault. 
down 
• The drive ramps down the motor in a controlled manner. 
Current high 
The drive output current is above the limit set in parameter 4‐51 Warning Current High. 
Current low 
The drive output current is below the limit set in parameter 4‐52 Warning Speed Low. 
DC hold is selected in parameter 1‐80 Function at Stop and a stop command is active. The 
DC hold 
motor is held by a DC current set in parameter 2‐00 DC Hold Current. 
The motor is held with a DC current (parameter 2‐01 DC Brake Current) for a specified time 
(parameter 2‐02 DC Braking Time). 
• DC brake is activated in parameter 2‐03 DC Brake Cut In Speed RPM and a stop command is 
DC stop 
active. 
• DC brake (inverse) is selected as a function for a digital input (parameter group 5–1* Digital 
Inputs). The corresponding terminal is not active. 
• The DC brake is activated via serial communication. 
In par. 1‐01 Motor Control Principle U/f and in par. 1‐80 Function at Stop DC‐Voltage U0 is 
DC Voltage U0 
selected. A Stop command (e.g. Stop (inverse)) is activated. The Voltage selected according to 
the par. 1‐55 U/f Characteristic ‐ U 0 (U/f‐Characteristic – UV) is applied to the Motor. 
The sum of all active feedbacks is above the feedback limit set in parameter 4‐57 Warning 
Feedback high 
Feedback High. 
The sum of all active feedbacks is below the feedback limit set in parameter 4‐56 Warning 
Feedback low 
Feedback Low. 
In par. 1‐73 Flying Start the Flying start function is activated. The FC is searching for the 
unknown shaft speed of the connected motor, within the adjusted speed range. The process 
Flying start 
was started by a start command, re‐connecting a digital input (parameter group 5–1* Digital 
Inputs) programmed as Coast inverse or by connecting the Mains. 
 
 
 
Description 