Conn.  
Term.  
1, 2 
X56
3‐12 
5, 6, 7 
X57 
10 
1, 2 
3, 4 
X59 
7, 8 
Terminal(s) 
Parameter 
P 5‐40 
1, 2  
P 5‐41 
P 5‐42 
19 
P 5‐11 
18 
P 5‐10 
P 5‐01
27 
P 5‐12
P 5‐02
29 
P 5‐31
Note: If the drive is reinitialized, be sure to change P 0‐03 Regional Settings to [1] North America and change the 
highlighted parameter values above for proper bypass operation. All other listed parameters are default values. 
ECB Control Card Terminal Functions 
Function 
N.O. contacts for running in bypass or drive 
Factory use only 
Digital input for safety stop 
Common 
Factory use only 
No function 
Factory use only 
Digital input for remote bypass enable 
Digital input overrides system to Bypass Mode ignoring all 
other inputs and commands, except for safety stop on 
terminal 1. 
Digital input for remote overload reset 
Common for binary I/O 
No function 
Digital output indicates panel is in Drive Mode. 
Digital output indicates panel is in Bypass Mode 
Common for binary I/O 
ECB Control Card Parameter Settings 
Name 
RELAY 1 – Function 
RELAY 1 – On Delay 
RELAY 1 – Off Delay 
Terminal 19 Digital Input 
Terminal 18 Digital Input 
Terminal 27 Mode 
Terminal 27 Digital Input
Terminal 29 Mode 
Terminal 29 Digital Output
Value 
[167] Start Command Active 
0.01 s 
0.01 s 
[52] Run permissive 
[8] Start
[0] Input 
[7] External Interlock
[1] Output 
[160] No Alarm
37
Type 
Relay output for user 
User supplied dry contact 
User supplied dry contact 
User supplied dry contact 
User supplied dry contact 
User supplied dry contact 
24 V DC digital output 
24 V DC digital output 
Function 
Run permissive 
Common run/stop 
External interlock 
Auto bypass 