Terminal Block Functions & Programming (P 0‐03 North American Default) 
Digital Input / Output Connector
[12,13] +24VDC 
[18] Start (P 5‐10) 
[19] No Operation (P 5‐11) 
[27] Ext. Interlock (P 5‐12) 
[29] Jog (P 5‐13) 
[32] No Operation (P 5‐14) 
Relay Terminal Block Functions (P 0‐03 North American Default) 
[01] Relay 1 COMMON 
[02] Relay 1 Normally Open 
[03] Relay 1 Normally Closed 
NOTE: Relay 1 default programming 
is set to [160] No Alarm (Energized 
when drive is NOT in alarm state) 
[61] SIG COM 
[37] 
STO (P 5‐
[20] DI Common 
[33] No Operation (P 5‐15) 
[68] (+) RS485 Interface 
[69] (‐) RS485 Interface 
Functions for Relay 1 & Relay 2 programmed in P 5‐4* 
 
Serial Comm. Connector
 
 
 
 
 
 
[39] AO Common 
 
 
[42] AO Speed (P 6‐50) 
19) 
 
 
[50] +10VDC 
 
[53] 
Ref Resource 1 (P 6‐1*)
 
[54] Feedback (P 6‐2*) 
 
 
[55] AI Common 
 
 
 
 
 
 
 
 
 
 
[06] Relay 2 Normally Closed 
 
 
[05] Relay 2 Normally Open 
 
[04] Relay 2 COMMON 
 
NOTE: Relay 2 default programming 
is set to [5] Running (Energized when 
 
drive is running) 
 
 
 
 
 
9
Analog Input / Output Connector
 