Reading from a drive 
 
Drives that were previously programmed and operating in the field can be backed up to an MCT 10 
project file. There are 2 ways to accomplish this. To back up a drive's active parameter settings to 
project file, follow the instructions listed below.  
 
 
Method 1 
 Connect to a live drive via USB or serial communication 
 Highlight the connected drive with the mouse 
 Right click, select Copy and wait until it's finished 
 Highlight the project, right click and select Paste 
 
Method 2 
 Open MCT 10 and create a new project drive that mimics the actual drive 
 Highlight the project drive of interest that has default settings 
 Right click, select Read from Drive and wait until it's finished 
 
The project drive will now have the same parameter settings as the actual drive. You can save the 
project (File –> Save As) to your laptop and the settings will now be securely stored.  
 
 
This guide is just a basic introduction of MCT 10 setup software functionality, and there are many 
other features that have not been discussed. Take some time to explore the software and uncover 
some useful features on your own. Right clicking will often bring up other available options 
including comparisons, scope traces, copy & paste features and a whole lot more. 
 