Download Print this page

Danfoss VLT HVAC Drive Instruction Manual page 27

Hide thumbs Also See for VLT HVAC Drive:

Advertisement

 
1. Initialize the drive to reset all parameters to the factory default values. Refer to Lab # 1 for 
initialization sequence if needed. If continuing from Lab # 1, you may go directly to step # 
5. 
 
2. Exit the Smart Start wizard by pressing Status and then OK.  
 
3. Press the Off button on LCP to prevent unintended operation during setup. 
 
4. Change P 0‐03 to [1] North America. Ignore the Alarm 60 for now. 
 
5. Go to the Q2 Quick Setup menu. Enter the following data: 
 
Parameter 
P 0‐01 
Language 
P 1‐21 
Motor Power HP 
P 1‐22 
Motor Voltage 
P 1‐23 
Motor Frequency 
P 1‐24 
Motor Current 
P 1‐25 
Motor Nominal Speed 
P 1‐28 
Motor Rotation Check 
P 3‐41 
Ramp 1 Ramp Up Time 
P 3‐42 
Ramp 1 Ramp Down Time 
P 4‐12 
Motor Speed Low Limit 
P 4‐14 
Motor Speed High Limit 
P 3‐11 
Jog Speed 
P 5‐12 
Terminal 27 Digital Input 
P 5‐40 [0]  Function Relay 1 
P 5‐40 [1]  Function Relay 2 
1‐29 
AMA Auto Motor Adaptation 
 
Note: AMA cannot be completed with the field demo motors. 
If you are using a field demo motor, skip to Verifying Operation.
 
6. Press the Hand On button. You will notice that the drive still won't run because it is being 
commanded to coast via Digital Input 27. This is shown on the status line at the bottom of 
the LCP. Coast Inverse means that the coast function will be executed when voltage is 
removed from the input, rather than applied.  
 
7. Turn ON switch DIN3/27 on the control box, which will apply +24 Vdc to Digital Input 27. 
When the switch is closed, the coast command will go away. 
 
8. Press the Hand On button to start the AMA function, and wait until the process has 
finished. 
 
9. After the AMA is complete, press the OK key and continue to Verifying Operation. 
Software Setup  
Description 
English 
0.33 Hp 
230 V 
60 Hz 
0.30 A 
1750 RPM 
[0] Off 
5 sec 
5 sec 
15 Hz 
60 Hz 
10 Hz 
[2] Coast inverse 
[160] No alarm 
[5] Running 
[0] Off 
26
Field Demo Motors 
English 
0.75 Hp 
230 V 
60 Hz 
2.90 A 
1750 RPM 
[0] Off 
5 sec 
5 sec 
15 Hz 
60 Hz 
10 Hz 
[2] Coast inverse 
[160] No alarm 
[5] Running 
[1] Enable Complete AMA 
Training Lab Motors 
 