Danfoss VLT HVAC Drive Instruction Manual page 36

Hide thumbs Also See for VLT HVAC Drive:

Advertisement

Conn.  
Term.  
Input/Output   
1, 2 
Input 
3, 4 
Input 
5, 6 
Input 
X55 
7, 8 
Input 
9, 10 
Output 
11, 12 
Output 
1, 2 
Output 
3, 4 
Output 
5, 6 
Output 
Output 
X56 
Output 
Output 
10 
Input 
11 
Input 
12 
Input 
X58 
1, 2 
Output 
Terminal(s) 
Parameter 
P 5‐40 
1, 2  
P 5‐41 
P 5‐42 
19 
P 5‐11 
18 
P 5‐10 
P 5‐00 
27 
P 5‐01 
P 5‐12 
P 5‐02 
29 
P 5‐31 
Note: If the drive is reinitialized, be sure to change P 0‐03 Regional Settings to [1] North America and change the 
highlighted parameter values above for proper bypass operation. All other listed parameters are default values. 
Name 
Remote Drive Start (with common start/stop) 
Remote Drive Start (without common start/stop) 
Motor Running on Drive 
Run request (for run permissive) 
Run Enable (for run permissive) 
Safety Stop 
Drive Fault 
Fire Mode 
Remote Motor 1 Select 
Remote Motor 2 Select 
Motor 1 Selected 
Motor 2 Selected 
Drive Mode 
Bypass Mode 
Fire Mode 
EMB2 Control Card Terminal Functions 
Type 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Common form C relay contact 
Normally closed form C relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
Normally open, dry relay contact 
EMB2 Control Card Parameter Settings 
Name 
RELAY 1 – Function 
RELAY 1 – On Delay 
RELAY 1 – Off Delay 
Terminal 19 Digital Input 
Terminal 18 Digital Input 
Digital I/O Mode 
Terminal 27 Mode 
Terminal 27 Digital Input 
Terminal 29 Mode 
Terminal 29 Digital Output 
EMB2 Control Card Typical Control Connections 
Input Command 
Input Command 
Output Status 
Output Command 
Input Command 
Input Command 
Output Status 
Input Command 
Input Command 
Input Command 
Output Status 
Output Status 
Output Status 
Output Status 
Output Status 
Closed when motor can start to run 
Closed for remote start with common start/stop 
Safety input, open to stop 
Closed to enable Fire Mode 
Closed indicates Fire Mode activated 
Closed indicates Motor 1 selected 
Closed indicates Motor 2 selected 
Closed when panel is in Drive Mode 
Closed when panel is in Bypass Mode 
Open when drive is in Fault Condition 
Common for fault relay 
Closed when drive is in Fault Condition 
CMS Motor 2, close to select 
CMS common 
CMS Motor 1, close to select 
Closed indicates run requested 
 
 
Value 
[167] Start Command Active 
0.01 s 
0.01 s 
[52] Run permissive 
[8] Start 
[0] PNP ‐ Active at 24V 
[0] Input 
[7] External Interlock 
[1] Output 
[160] No Alarm 
 
 
Drive 
Function 
Terminals  
  
13, 18 
04, 05, 06 
  
  
  
  
  
  
  
  
  
  
  
  
 
 
35
Function 
Function 
Run permissive 
Common run/stop 
External interlock 
Auto bypass 
EMB2 
EMB2 
EMB2 
X56  
X55  
X58 
  
3, 4 
  
  
  
  
  
  
  
  
  
1, 2 
  
1, 2 
  
  
5, 6 
  
7, 8, 9 
  
  
  
7, 8 
  
11, 12 
  
  
10, 11 
  
  
  
11, 12 
  
1, 2 
 
  
3, 4 
 
  
5, 6 
 
  
 
  
9, 10  