Download Print this page

Danfoss VLT HVAC Drive Instruction Manual page 13

Hide thumbs Also See for VLT HVAC Drive:

Advertisement

Danfoss FC Series Quick Start‐up Sheet 
1. Set Main Menu P 0‐03 to [1] North America. Ignore the Alarm 60 for now.
 
2. Place a jumper wire between terminals 12 & 27 if a safety interlock will not be used. 
Alternatively, programming terminal 27 via P 5‐12 to the value [0] No operation will 
eliminate the need for a contact. If a Normally Closed safety contact will be used, wire it 
between terminals 12 & 27 and program it accordingly. Press the reset key to clear the 
Alarm 60 if it is still present. 
 
3. Press the Quick Menu button, then go to Q2 Quick Setup to enter the following items. 
 
Parameter 
P 0‐01 
Language 
P 1‐21 
Motor Power HP 
P 1‐22 
Motor Voltage 
P 1‐23 
Motor Frequency 
P 1‐24 
Motor Current 
P 1‐25 
Motor Nominal Speed 
P 1‐28 
Motor Rotation Check 
P 3‐41 
Ramp 1 Ramp‐Up Time 
P 3‐42 
Ramp 1 Ramp‐Down Time 
P 4‐12 
Motor Speed Low Limit 
P 4‐14 
Motor Speed High Limit 
P 3‐11 
Jog Speed 
P 5‐12 
Terminal 27 Digital Input 
P 5‐40 
Function Relay 
P 1‐29 
Automatic Motor Adaptation (AMA) 
NOTE: It is recommended to always enable a complete AMA to tune the drive to the motor and improve performance. 
 
4. Wire a start switch or contact between terminals 12 & 18. 
 
5. Wire the speed reference on terminals 53 & 55 (+ on 53, common on 55). 
NOTE: Remove the LCP and verify that the DIP switch for AI53 is set to the correct position. For voltage signals 
it should remain in the default position, to the left. For current reference signals move it to the right position.  
Be sure to scale the input to match the reference signals via P 6‐1*. 
 
6. In North American defaults, Relay 1 is programmed for [160] No Alarm. Wire between 
terminals 1 & 3 for Alarm indication. Relay 2 is programmed for [5] Running. Wire 
between terminals 4 & 5 for Run indication. Use P 5‐4* to select different relay functions, if 
desired. 
 
7. The drive is ready to run at this point. The parameters listed below may enhance the 
setup and can be used if desirable.
 
Parameter 
Name 
P 1‐73 
Flying Start 
P 22‐60 
Broken Belt Function 
P 22‐61 
Broken Belt Torque 
P 4‐6* 
Bypass Speed 
 
8. Set P 0‐50 LCP Copy to All To LCP to copy all parameters to the keypad. 
Description 
RPM  Enter motor nominal speed 
 
Select to catch a spinning motor when it receives a start signal 
Select an action if a broken belt is detected 
Set broken belt torque as percentage of the motor torque 
Select motor speed range to avoid due to resonant frequencies 
Unit 
  
Select desired LCP menu language 
HP 
Enter motor horsepower 
Enter motor voltage 
Hz 
Enter motor frequency 
Enter motor current 
Hz 
Allows motor rotation direction to be verified 
Enter desired motor ramp‐up time (in seconds) 
Enter desired motor ramp‐down time (in seconds) 
Hz 
Enter desired minimum motor shaft speed 
Hz 
Enter desired maximum motor shaft speed 
Hz 
Enter desired fixed output speed for jog function 
  
Select desired Digital Input function (See step 2 above) 
 
Array parameter, 0=Relay1, 1=Relay 2 
  
Select desired automatic motor tuning function 
Description
12
 
Notes 
 

Advertisement

loading