7. There is a collection of commonly used parameters in the Q2 Quick Setup menu. Use the 
up and down arrow buttons to scroll through the following parameters and enter the 
following data: 
 
Parameter 
P 0‐01 
Language 
P 1‐21 
Motor Power HP 
P 1‐22 
Motor Voltage 
P 1‐23 
Motor Frequency 
P 1‐24 
Motor Current 
P 1‐25 
Motor Nominal Speed 
P 1‐28 
Motor Rotation Check 
P 3‐41 
Ramp 1 Ramp Up Time 
P 3‐42 
Ramp 1 Ramp Down Time 
P 4‐12 
Motor Speed Low Limit 
P 4‐14 
Motor Speed High Limit 
P 3‐11 
Jog Speed 
P 5‐12 
Terminal 27 Digital Input 
P 5‐40 
Function Relay [0] 
P 1‐29 
AMA Auto Motor Adaptation  [0] Off 
 
Note that any of these parameters can be accessed through the drive's Main Menu as well. 
 
Note: AMA cannot be completed with the field demo motors. 
If you are using a field demo motor, skip to Verifying Operation. 
8. Before running the Automatic Motor Adaptation (AMA) function, record the values listed 
for the parameters in the following chart in the Values Prior to AMA column. 
Parameter 
P 1‐30 
Stator Resistance (Rs) 
P 1‐31
Rotor Resistance (Rr) 
P 1‐35
Main Reactance (Xh) 
P 1‐36
Iron Loss Resistance (Rfe) 
 
9. The last step in the Q2 Quick Setup is to run the Automatic Motor Adaptation (AMA) 
function. Set P 1‐29 to the value [1] Enable Complete AMA. The AMA is a special software 
function that will perform a dynamic test and will fine tune the drive to match the 
connected motor and cabling. The AMA sequence provides the drive with a more accurate 
motor model than simply entering the basic data in parameter group  P 1‐2*. 
 
10. Press the Hand On button to start the AMA function, and wait until the process has 
finished. 
 
11. After the AMA is complete, press the OK key. Record the values listed for the parameters 
in the chart from step # 8 in the Values After AMA column.  
Have the values changed? _____________ 
Why?_____________________________________________________________________ 
 
12. Continue to Verifying Operation. 
Description 
English 
0.33 Hp 
230 V 
60 Hz 
0.30 A 
1750 RPM 
[0] Off 
5 sec 
5 sec 
0 Hz 
60 Hz 
10 Hz 
[0] No operation 
[6] Running / no warning 
Name 
 
 
 
 
Field Demo Motors 
 
 
Values Prior to AMA 
20
Training Lab Motors 
English 
0.75 Hp 
230 V 
60 Hz 
2.90 A 
1750 RPM 
[0] Off 
5 sec 
5 sec 
0 Hz 
60 Hz 
10 Hz 
[0] No operation 
[6] Running / no warning 
GO TO STEP # 8 
Values After AMA 
 
 
 
 