Danfoss VLT HVAC Drive Instruction Manual page 30

Hide thumbs Also See for VLT HVAC Drive:

Advertisement

1. Connect the motor to the drive. 
 
2. Connect the I/O Test Box to the control card & relays. Ensure all DIN switches are turned 
OFF. 
 
3. Plug in the demo drive's power cord into a 120 Vac outlet. 
 
Note: The I/O Test Box will simulate the BMS signals. Switches DIN1/18 through DIN6/33 will be used to 
apply +24 Vdc to the drive's digital inputs for activation. For the VLT HVAC drive to run in a closed loop 
configuration, it must have a pressure transducer wired directly to it. This lab is only a simulation of an 
HVAC application, so there will be no actual pressure. In order to simulate the pressure feedback, a 2‐10 Vdc 
signal will be input to the drive by means of a potentiometer on the control box. 
 
 
1. Initialize the drive to reset all parameters to the factory default values. Refer to Lab # 1 for 
initialization sequence if needed. If continuing from Lab # 2, you may go directly to step # 
5. 
 
2. Exit the Smart Start wizard by pressing Status and then OK. What alarm did initializing the 
drive cause? 
 
3. Press the Off button on the LCP to prevent unintended operation during setup. 
 
4. Change P 0‐03 to [1] North America. Ignore the Alarm 60 for now. 
 
5. Go to the Q2 Quick Setup menu. Enter the following data: 
 
Parameter 
P 0‐01 
Language 
P 1‐21 
Motor Power HP 
P 1‐22 
Motor Voltage 
P 1‐23 
Motor Frequency 
P 1‐24 
Motor Current 
P 1‐25 
Motor Nominal Speed 
P 1‐28 
Motor Rotation Check 
P 3‐41 
Ramp 1 Ramp Up Time 
P 3‐42 
Ramp 1 Ramp Down Time 
P 4‐12 
Motor Speed Low Limit 
P 4‐14 
Motor Speed High Limit 
P 3‐11 
Jog Speed 
P 5‐12 
Terminal 27 Digital Input 
P 5‐40 [0]  Function Relay 1 
P 5‐40 [1]  Function Relay 2 
1‐29 
AMA Auto Motor Adaptation 
Mechanical Setup 
Software Setup 
Description 
Note: AMA cannot be completed with the field demo motors.  
If you are using a field demo motor, skip to Step 10. 
 
Field Demo Motors 
English 
0.33 Hp 
230 V 
60 Hz 
0.30 A 
1750 RPM 
[0] Off 
5 sec 
5 sec 
15 Hz 
60 Hz 
10 Hz 
[2] Coast inverse 
[160] No alarm 
[8] Run on ref / no warning  [8] Run on ref / no warning 
[0] Off 
 
29
Training Lab Motors 
English 
0.75 Hp 
230 V 
60 Hz 
2.90 A 
1750 RPM 
[0] Off 
5 sec 
5 sec 
15 Hz 
60 Hz 
10 Hz 
[2] Coast inverse 
[160] No alarm 
[1] Enable Complete AMA 