GROUP 3 – Third (right) word: Operation Status 
Operation status               
The motor is accelerating/decelerating using the active ramp up/down. The reference, a limit 
Ramping 
value, or a standstill is not yet reached. 
The sum of all active references is above the reference limit set in parameter 4‐55 Warning 
Ref. high 
Reference High. 
The sum of all active references is below the reference limit set in parameter 4‐54 Warning 
Ref. low 
Reference Low. 
Run on ref. 
The drive is running in the reference range. The feedback value matches the setpoint value. 
A start command has been given, but the motor is stopped until a run permissive signal is 
Run request 
received via digital input. 
Running 
The drive is driving the motor. 
(FC 100/200 only) The boost function in parameter 4‐06 Boost setpoint is enabled. This 
Sleep Boost 
function is only possible in 
Closed loop operation. 
The energy‐saving function is enabled. This function being enabled means that now the 
Sleep mode 
motor has stopped, but that it restarts automatically when required. 
The output frequency is corrected by the value set in par. 3‐12 Catch up/slow Down Value. 
1. Slow Down was selected as a function for a digital input (parameter group 5–1* Digital 
Slow down 
Inputs). The corresponding terminal is active. 
2. Slow Down was activated via serial communication. 
Speed high 
The motor speed is above the value set in parameter 4‐53 Warning Speed High. 
Speed low 
The motor speed is below the value set in parameter 4‐52 Warning Speed Low. 
In auto‐on mode, the drive starts the motor with a start signal from a digital input or serial 
Standby 
communication. 
In parameter 1‐71 Start Delay, a delay starting time was set. A start command is activated, 
Start delay 
and the motor starts after the start delay time expires. 
12 Enable Start Forward and 13 Enable Start Reverse were selected as functions for 2 
Start fwd/rev 
different digital inputs (parameter group 5–1* Digital Inputs). The motor starts in forward or 
reverse depending on which corresponding terminal is activated. 
PROFIDrive profile was selected in par. 8‐10 Control Word Profile. The start inhibition is 
Start inhibit 
active. The FC needs the first part (e.g. 0x047E) of the two‐part start command via serial 
communication to allow starting. See also operation status control ready. 
The drive has received a stop command from one of the following: 
• LCP. 
Stop 
• Digital input. 
• Serial communication. 
An alarm occurred and the motor is stopped. Once the cause of the alarm is cleared, reset 
the drive using 1 of the following: 
Trip 
• Pressing Reset. 
• Remotely by control terminals. 
• Via serial communication. 
An alarm occurred and the motor is stopped. Once the cause of the alarm is cleared, cycle 
power to the drive. Reset the drive manually by one of the following: 
Trip lock 
• Pressing Reset. 
• Remotely by control terminals. 
• Via serial communication. 
PROFIDrive profile was selected in par. 8‐10 Control Word Profile. A Control word is sent to 
Unit/Drive not 
the FC via serial communication with Off 1, Off 2 and Off 3 active. Start inhibit is active. To 
ready 
enable Start, see operation status Start inhibit. 
 
 
 