Epever UPower-HI Series User Manual page 43

Inverter/charger
Hide thumbs Also See for UPower-HI Series:
Table of Contents

Advertisement

Under
voltage
36
warning
voltage
AGM(Default)/GEL/FLD: 48.0V
Utility over
voltage
37
disconnec
tion
voltage
Utility low
voltage
38
disconnec
tion
voltage
Battery
discharge
current
39
limit
Refer to
3.7 for
details.
lithium
battery
40
protocol
type
LFP15: 49.2V
LFP16: 52.4V
LCNM14: 53.4V
AGM(Default)/GEL/FLD: 24.0V
LFP8: 25.7V
LCNM7: 26.2V
LFP15: 48.2V
LFP16: 51.4V
LCNM14: 52.4V
User define for the 24V system: 21.6~32.0V
Step size: long press for 1V,short press for 0.1V
User define for the 48V system: 43.2~64.0V
Step size: long press for 1V,short press for 0.1V
132.0V (Default for the 110V system ) User
define: 110VAC~140VAC
Step size: long press for 10V,short press for 1V
264.0V (Default for the 220V system ) User
define: 220VAC~290VAC
Step size: long press for 10V,short press for 1V
88.0V (Default for the 110V system ) User
define: 80VAC~110VAC
Step size: long press for 10V,short press for 1V
176.0V(Default for the 220V system ) User
define: 90VAC~190VAC
Step size: long press for 10V,short press for 1V
UP2000-HM6021/UP2000-HM6022:
200A(Default) User define: 10~200A
UP3000-HM5041/UP3000-HM5042/UP3000-HM
8041: 150A(Default) User define:10~150A
UP3000-HM10021/UP3000-HM10022:
300A(Default) User define: 10~300A
UP5000-HM8042:
define:10~250A
Step size: Long press for 10A,short press for 1A
1(Default)
User Define:1~10
NOTE: Refer to the (3) Lithium battery BMS Interface
of chap 1
41
250A(Default)
User

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents