SE LP10 Mortise Lock
Specifications / Features (Continued)
4
• UL Listed* - UL 294 Indoor Use
• CUL Listed - S319: Class 1
• ANSI/BHMA A156.25 Listed
Grade 1 Compliant
*UL294, S319, & BHMA A156.25 currently not applicable
to Alternate Indicator Configuration option
Electrical Specifications
12/24VDC System
Reader
Actuator
The reader requires 12VDC for power, while the lock
accepts either 12 or 24VDC.
Total
Wire Gauge Chart 12VDC
One-Way
Length of
Wire Run (ft)
1/4A
1/2A
3/4A
100
20
18
150
18
16
200
16
14
250
16
14
300
16
12
400
14
12
500
14
10
750
12
10
1,000
10
1,500
10
Wiring methods shall be in accordance with the National Electrical Code (ANSI/NFPA70), CSA 22.1, Canadian Electrical
Code (CEC), Part I, Safety Standard for Electrical Installations, local codes and the authorities having jurisdiction.
This product is not intended for outside wiring as covered by Article 800 in the National Electrical Code, NFPA 70.
A8113H • 800-810-WIRE (9473) • www.sargentlock.com
12V
Average
Peak
Average
100mA
220mA
n/a
15mA
500mA
15mA
Load Current @ 12VDC
1A
1-1/4A
1-1/2A
2A
16
14
14
12
12
14
12
12
12
10
12
12
10
10
12
10
10
10
12
10
10
10
10
• UL 294 Access Control Ratings:
Destructive Attack
Line Security
Endurance
Standby Power
UL testing was conducted on product powered by
UL Listed model 9001GR/AC injector; manufactured
by Microsemi Corp.
24V
Peak
n/a
500mA
McKinney
Electric
Hinge
Total
Wire Gauge Chart 24VDC
One-Way
Length of
3A
Wire Run (ft)
1/4A
1/2A
10
100
24
20
150
22
18
200
20
18
250
18
16
300
18
16
400
18
14
500
16
14
750
14
12
1,000
14
10
1,500
12
10
5
Level 1
Level 1
Level 4
Level 1
Wiegand Access
Control System
SE LP10
Load Current @ 24VDC
3/4A
1A
1-1/4A
1-1/2A
2A
18
18
16
16
14
16
16
14
14
12
16
14
14
12
12
14
14
12
12
12
14
12
12
12
10
12
12
10
10
12
10
10
10
10
10
3A
12
10
10
10