SE LP10 Mortise Lock
Operational Check (Continued)
8
Note: Once electrical wiring has been successfully completed
according to proper application, perform the following steps:
A. Ensure lock is interfaced with Wiegand Test Unit to verify installation
and wiring up to (frame side) point of hinge.
B. Turn power ON.
C. Wait for LED to turn RED and then present compatible credential
and verify LED and sounder activity.
D. Verify valid card read on Wiegand Test Unit or at the EAC panel.
E. Verify system operation functions; i.e., when credential is presented
to reader, the door should unlock.
NOTE: Ensure LED operates as configured*:
LED remains green when panel asserts GREEN_LED signal
*For configurations with Alternate Indicator override enabled; see Application Diagram #2 in Section 6.
If the lock fails to operate when DC voltage is applied:
A. Remove power.
B. Confirm the polarity of the supply (i.e., '+' is positive).
If the lock is functioning opposite to the desired fail-safe or fail-secure operation:
A. Remove power and check the "Fail" condition by attempting to rotate the outside lever
(e.g. if fail-secure, the outside lever should be rigid with power removed).
B. If the function is incorrect, remove the lock and repeat section 6, step 3 (DIP Switch configuration).