Sungrow SG2.0RS-S User Manual page 81

1-phase pv grid-connected inverter
Hide thumbs Also See for SG2.0RS-S:
Table of Contents

Advertisement

User Manual
A A l l a a r r m m I I D D
003
004
005
006
007
A A l l a a r r m m N N a a m m e e
C C o o r r r r e e c c t t i i v v e e M M e e a a s s u u r r e e s s
Grid
Generally, the inverter will be reconnected to the
overfrequency
grid after the grid recovers. If the alarm occurs
frequently:
1. Measure the grid frequency, and contact the
local utility grid company for solutions if the grid
Grid
frequency is beyond the specified range.
underfrequency
2. Check, through the App, whether the protection
parameters are appropriately set.
3. If the alarm persists, contact SUNGROW.
Generally, the inverter will be reconnected to the
grid after the grid recovers. If the alarm occurs
frequently:
1. Check whether the grid supplies power reliably.
2. Check whether the AC cable is firmly in place.
No Grid
3. Check whether the AC cable is correctly
connected (whether the live wire and the N wire
are in correct place).
4. Check whether the AC switch or circuit breaker
is disconnected.
5. If the alarm persists, contact SUNGROW.
1. The alarm can be caused by poor sunlight or
damp environment, and the inverter will be
reconnected to the grid after the environment is
Overhigh
improved.
leakage current
2. If the environment is normal, check whether the
AC and DC cables are well insulated.
3. If the alarm persists, contact SUNGROW.
Generally, the inverter will be reconnected to the
grid after the grid recovers. If the alarm occurs
frequently:
1. Measure the grid frequency, and contact the
Grid abnormal
local utility grid company for solutions if the grid
frequency exceeds the specified value.
2. If the alarm persists, contact SUNGROW.
9 Troubleshooting and Maintenance