Checking The Connections On The Battery Converter; Checking The Battery Modules; Checking The Replacement Power Network; Black Start Key Test - Varta element backup 6 Operating Manual

Hide thumbs Also See for element backup 6:
Table of Contents

Advertisement

11.13.3

Checking the connections on the battery converter

Check whether the system reports a current flow (realistic currents) on all three phases.
There is a fault if the value for the current (I network) oscillates between +0.01 and ­0.01 on all three phases.
Check the cable connection to the current sensor.
Note: The system may need to be charged with a large consumer on all three phases.
11.13.4

Checking the battery modules

Check whether the battery module serial numbers of all installed battery modules are displayed.
11.14

Checking the replacement power network

Connect the intended consumers to the replacement power network.
Switch off the store fuse (F1 in the connection diagram).
The store should automatically go into backup mode.
Interrupt the connection to the consumers for a few seconds.
Check whether the replacement power network was developed and the consumers are in operation.
Note: Remember that some consumers change operating mode only after a few minutes. Test the replacement
power network over a sufficiently long time.
Check in the web interface whether error messages are displayed.
Fault remedy: Possibly inrush current too great. Reduce the consumers and carry out the check again.
Fault remedy: Possibly continuous load too great. Reduce the consumers and carry out the check
again.
11.15

Black start key test

3.
Switch off the energy store.
4.
Switch off the store fuse (F1 in the connection diagram).
5.
Switch on the energy store.
6.
Press the black start button.
The store should automatically go into backup mode.
Check whether the replacement power network was developed and the consumers are in operation.
Note: Remember that some consumers change operating mode only after a few minutes. Test the replacement
power network over a sufficiently long time.
Check in the web interface whether error messages are displayed.
Fault remedy: Possibly inrush current too great. Reduce the consumers and carry out the check again.
Fault remedy: Possibly continuous load too great. Reduce the consumers and carry out the check
again.
73