11.8.1

Replacement power connection preparation (light grey plug)

For the replacement power connection, the 5-wire replacement power connection line must be connected to
the
plug connection (light-grey plug) provided.
Strip the connection line 40mm at the end.
The PE conductor must be 5mm longer than the other four conductors (L1, L2, L3, N). Shorten these
conductors accordingly.
Strip the five wires of the house connection at the ends 8mm.
In the case of fire-wired conductors, wire terminations are to be used.
Remove the plug housing: To this end, release the catch by pressing the two side detents
simultaneously.
Slide the cap nut and the plug housing over the line.
i