DAYLIFF EXPRESS D1-1ph Installation & Operating Manual page 27

Express electronic pump controller
Table of Contents

Advertisement

The load current absorption is higher than the set value and the panel
A L A R M M O T O R
I N P R O T E C T I O N
shuts down the relative pump.
The display and red led flash and the cumulative alarm output is
activated (voltage-free contacts NC-C-NO).
The system is reset manually by pressing the button SETUP until the
screen is displayed without flashing, after which the button OK can be
pressed to reset.
The thermal cutout of the motor (clicson) has tripped on temperature
A L A R M M O T O R
O V E R
overload.
T E M P E R AT U R E
The display and red led flash and the cumulative alarm output is
activated (voltage-free contacts NC-C-NO).
If not used, close the motor clicson input. (the pumps are not shut
down).
The system is reset manually by pressing the button SETUP until the
screen is displayed without flashing, after which the button OK can be
pressed to reset.
The measured mains voltage is too low (the pumps are shut down).
A L A R M V O LTA G E
T O O LO W
The display and red led flash and the cumulative alarm output is
activated (voltage-free contacts NC-C-NO).
The system is reset manually by pressing the button SETUP until the
screen is displayed without flashing, after which the button OK can be
pressed to reset.
The measured mains voltage is too high (the pumps are shut down).
A L A R M V O LTA G E
T O O H I G H
The display and red led flash and the cumulative alarm output is
activated (voltage-free contacts NC-C-NO).
The system is reset manually by pressing the button SETUP until the
screen is displayed without flashing, after which the button OK can be
pressed to reset.
The phase sequence is incorrect or one or more phases is missing (the
A L A R M
S E Q U E N C E
pumps are shut down).
O R L A C K
The display and red led flash and the cumulative alarm output is
P H A S E S
activated (voltage-free contacts NC-C-NO).
The system is reset automatically by turning the panel off and on again.
The alarm float detects maximum level reached (the pumps are not shut
A L A R M
M A X L E V E L
down).
The display and red led flash and the cumulative alarm output is
activated (voltage-free contacts NCC-
NO).
The system is reset manually by pressing the button SETUP until the
screen is displayed without
flashing, after which the button OK can be pressed to reset.
The alarm is repeated if the level does not fall.
6 6 6 23