Programming Menu
To select the panel operating logic, access the programming menu by pressing the buttons
SETUP, UP and DOWN at the same time on the main screen of the panel.
DESCRIPTION OF PARAMETER
Language
0 ITA / 1 ENG/ 2 FRA / 3 ESP
Operating Logic
Number of Pumps
This parameter enables selection of the number of pumps in the system
(when 1 single pump is selected, the parameter PUMP ROTATION
ENABLED is disabled).
Pump rotation enabled
This parameter enables activation of pump exchange on each demand
from floats or pressure switches. Also, if the main pump thermal cutout
(current overload) trips, the second pump is enabled.
Minimum Level Alarm Output
This parameter enables removal of the minimum level alarm from the
cumulative alarm output.
Sensor Sensitivity (Sa - Sb - Sc - Sd)
This parameter enables display of sensor sensitivity. With the contacts
open, if a value of 99 is displayed, and a value of 45 is displayed with
water present, set sensitivity to an intermediate value, such as 75.
Type Of Analogue Signal
This parameter enables selection of the type of analogue signal on input
to the panel:
0 = 0-10 V
Unit Of Measurement
This parameter enables selection of the measurement unit of the
analogue signal on input to the panel.
1 = 4-20 mA
15
VALUE
FAULT
0
0
5
-
As per order
1-4
Y or N
Y
Y or N
Y
0 - 99
75
As per order
0 or 1
% + or % -
As per order
m or bar