DESCRIPTION OF PARAMETER
Sequential Reset On Dry Running Alarm
If the value 0 (zero) is set, all automatic resets are blocked after the fourth
attempt; if the value is set to 1 (one) at the end of the fourth attempt, the reset
cycle is repeated continuously;
The system protecting the panel against dry running conditions activates the
reset cycle according to the time intervals set, and resumes the same reset
cycle each time water is detected for more than 10 seconds.
Set Point
This parameter enables entry of the set point for pressure (bar), level
(metres) or percentage to be maintained on the system. The maximum
settable value depends on the "ANALOGUE SIGNAL FULL SCALE" set in
the ASSISTANCE menu.
Threshold P1 / P2 / P3 / P4
In the case of pump P1, this indicates the restart value of the first pump
(master) on decrease or increase of the previously entered set point.
In the case of pumps P2, P3 and P4, this indicates the start and stop
values of the pumps used as backup units.
The maximum settable value depends on the "ANALOGUE SIGNAL FULL
SCALE" set in the ASSISTANCE menu.
Display Brightness On Standby
This parameter enables entry of the brightness setting applied when the
display sets to standby (wait 9 seconds for a preview).
Time For Entry To Set-up
This parameter enables entry of the time to keep the SETUP button
pressed for access to the set-up menu.
5.7 FUNCTION 7 - Filling with level sensors and oats/pressure switches
This operating mode is used for filling applications using level sensors and floats or
pressure switches, enabling the control of one pump. On selection of mode 7, all relative
parameter fields for this function are enabled.
6 6 6 19
VALUE
FAULT
0 or 1
0
-
0.0 - 999.9
As per order
0.0 - 999.9
0-9
4
2 - 30 Sec
3 Sec