User Menu
On completion of panel operation programming, enter the setup menu to configure the
various data for motor start-up. To access the user menu, press the button SETUP for 4
seconds in the main screen of the panel.
DESCRIPTION OF PARAMETER
Minimum Voltage
Set by default at -10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Voltage
Set by default at +10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Current P1 / P2 / P3 / P4
This parameter enables entry of the maximum current for each motor.
Enter the maximum current value, increasing it by 10-15% with respect to the
rated motor value.
Modifications to operating limits beyond the parameters stated on the model
data plate will immediately render the warranty null and void.
Set Point
This parameter enables entry of the set point for pressure (bar), level
(metres) or percentage to be maintained on the system.
The maximum settable value depends on the "ANALOGUE SIGNAL FULL
SCALE" set in the ASSISTANCE menu.
Threshold P1 / P2 / P3 / P4
In the case of pump P1, this indicates the restart value of the first pump
(master) on decrease or increase of the previously entered set point.
In the case of pumps P2, P3 and P4, this indicates the start and stop
values of the pumps used as backup units.
The maximum settable value depends on the "ANALOGUE SIGNAL FULL
SCALE" set in the ASSISTANCE menu.
Display Brightness On Standby
This parameter enables entry of the brightness setting applied when the
display sets to standby (wait 9 seconds for a preview).
Time For Entry To Set-up
This parameter enables entry of the time to keep the SETUP button
pressed for access to the set-up menu.
5.5 FUNCTION 5 - Pressurisation with analogue signal and level sensors
This operating mode is used for pressurisation applications managed via analogue
signals and level sensors, enabling the control of one or more pumps.
On selection of mode 5, all relative parameter fields for this function are enabled.
14
VALUE
FAULT
207 (230)
-
360 (400)
253 (230)
-
440 (400)
1 - ... A
As per order
-
0.0 - 999.9
-
0.0 - 999.9
0-9
4
2-30 Sec
3 Sec