DAYLIFF EXPRESS D1-1ph Installation & Operating Manual page 16

Express electronic pump controller
Table of Contents

Advertisement

DESCRIPTION OF PARAMETER
Minimum Voltage
Set by default at -10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Voltage
Set by default at +10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Current P1 / P2 / P3 / P4
This parameter enables entry of the maximum current for each motor.
Enter the maximum current value, increasing it by 10-15% with respect to the
rated motor value.
Modifications to operating limits beyond the parameters stated on the model
data plate will immediately render the warranty null and void.
Minimum COS-Phi P1 / P2 / P3 / P4
This parameter establishes the minimum Cos-Phi power factor value for
each motor
Enable operation in manual mode, activate in no-load conditions (dry
running), check the power factor reading (e.g. 0.65) and enter the
minimum power factor, increasing it by approx. 0.05.
Automatic Reset On Dry Running Alarm
In the event of a dry running alarm (minimum power factor) the panel
may attempt to reset automatically, which can be programmable in
minutes.
4 reset times can be set, in which the system automatically restarts after
being blocked; By default these values are set as shown below:
The first reset attempt is performed 5 minutes after the dry running alarm.
The second reset attempt is performed 10 minutes after the alarm.
The third reset attempt is performed 15 minutes after the alarm.
The fourth reset attempt is performed 20 minutes after the alarm.
Sequential Reset On Dry Running Alarm
If the value 0 (zero) is set, all automatic resets are blocked after the fourth
attempt; if the value is set to 1 (one) at the end of the fourth attempt, the
reset cycle is repeated continuously;
The system protecting the panel against dry running conditions activates
the reset cycle according to the time intervals set, and resumes the same
reset cycle each time water is detected for more than 10 seconds.
Display Brightness On Standby
This parameter enables entry of the brightness setting applied when the
display sets to standby (wait 9 seconds for a preview).
Time For Entry To Set-up
This parameter enables entry of the time to keep the SETUP button
pressed for access to the set-up menu.
5.4 FUNCTION 4 - Pressurisation with analogue signal and
oats/pressure switches
This operating mode is used for pressurisation applications managed via analogue
signals and floats or pressure switches, enabling the control of one or more pumps.
On selection of mode 4, all relative parameter fields for this function are enabled.
12
VALUE
FAULT
207 (230)
-
360 (400)
253 (230)
-
440 (400)
1 - ... A
As per order
0.15-1.00
0.8
1° 5 Min
2° 10 Min
1-240min
3° 20 Min
4° 30 Min
0 or 1
0
0-9
4
2-30 Sec
3 Sec