DAYLIFF EXPRESS D1-1ph Installation & Operating Manual page 24

Express electronic pump controller
Table of Contents

Advertisement

Programming Menu
To select the panel operating logic, access the programming menu by pressing the buttons
SETUP, UP and DOWN at the same time on the main screen of the panel.
DESCRIPTION OF PARAMETER
Language
0 ITA / 1 ENG/ 2 FRA / 3 ESP
Operating Logic
Sensor Sensitivity (Sa - Sb - Sc - Sd)
This parameter enables display of sensor sensitivity. With the contacts open, if
a value of 99 is displayed, and a value of 45 is displayed with water present,
s e t s e n s i t i v i t y t o a n i n t e r m e d i a t e v a l u e , s u c h a s 7 5 .
User Menu
On completion of panel operation programming, enter the setup menu to configure the
various data for motor start-up. To access the user menu, press the button SETUP for 4
seconds in the main screen of the panel.
DESCRIPTION OF PARAMETER
Minimum Voltage
Set by default at -10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Voltage
Set by default at +10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Current P1 / P2 / P3 / P4
This parameter enables entry of the maximum current for each motor.
Enter the maximum current value, increasing it by 10-15% with respect to the
rated motor value.
Modifications to operating limits beyond the parameters stated on the model
data plate will immediately render the warranty null and void.
Display Brightness On Standby
This parameter enables entry of the brightness setting applied when the
display sets to standby (wait 9 seconds for a preview).
Time For Entry To Set-up
This parameter enables entry of the time to keep the SETUP button
pressed for access to the set-up menu.
5.8 FUNCTION 8 - Filling with level sensors and "COS-Phi" power factor
control
This operating mode is used for filling applications with levels sensors, standard floats or
pressure switches and dry running safety control, obtained from the power factor (where
"Phi" is the timing angle between current and voltage), without the need for external
commands (float or pressure switch), enabling the control of one pump. On selection of
mode 8, all relative parameter fields for this function are enabled.
6 6 6 20
VALUE
FAULT
0
0
7
-
75
0-99
VALUE
FAULT
207 (230)
-
360 (400)
253 (230)
-
440 (400)
1 - ... A
As per order
0 - 9
4
2 - 30 Sec
3 Sec