Programming Menu

To select the panel operating logic, access the programming menu by pressing the buttons
SETUP , UP and DOWN at the same time on the main screen of the panel.
DESCRIPTION OF PARAMETER
Language
0 ITA / 1 ENG/ 2 FRA
Operating Logic
Number of Pumps
This parameter enables selection of the number of pumps in the system
(when 1 single pump is selected, the parameters pump rotation enabled and
float star/stop function are disabled).
Pump rotation enabled
This parameter enables activation of pump exchange on each demand
from floats or pressure switches. Also, if the main pump thermal cutout
(current overload) trips, the second pump is enabled (if set to N,
parameter 5 is disabled).
Float start/stop function (self-holding)
This parameter enables deactivation of active pumps only on opening of
the contact MIN.F. (min./stop float).
Minimum level alarm output
This parameter enables removal of the minimum level alarm from the
cumulative alarm output.
User Menu
On completion of panel operation programming, enter the setup menu to configure the
various data for motor start-up. To access the user menu, press the button SETUP for 4
seconds in the main screen of the panel.
7
VALUE
FAULT
0
0
1
-
As per order
1-4
Y or N
Y
Y or N
N
Y or N
Y