DAYLIFF EXPRESS D1-1ph Installation & Operating Manual page 13

Express electronic pump controller
Table of Contents

Advertisement

Programming Menu
To select the panel operating logic, access the programming menu by pressing the buttons
SETUP, UP and DOWN at the same time on the main screen of the panel.
DESCRIPTION OF PARAMETER
Language
0 ITA / 1 ENG/ 2 FRA
Operating Logic
Number of Pumps
This parameter enables selection of the number of pumps in the system
(when 1 single pump is selected, the parameter PUMP ROTATION
ENABLED is disabled).
Pump rotation enabled
This parameter enables activation of pump exchange on each demand
from floats or pressure switches. Also, if the main pump thermal cutout
(current overload) trips, the second pump is enabled.
Sensor Sensitivity (Sa - Sb - Sc - Sd)
This parameter enables display of sensor sensitivity. With the contacts open,
if a value of 99 is displayed, and a value of 45 is displayed with water
present, set sensitivity to an intermediate value, such as 75.
Minimum Level Alarm Output
This parameter enables removal of the minimum level alarm from the
cumulative alarm output.
User Menu
On completion of panel operation programming, enter the setup menu to configure the
various data for motor start-up. To access the user menu, press the button SETUP for 4
seconds in the main screen of the panel.
9
VALUE
FAULT
0
0
2
-
As per order
1-4
Y or N
Y
0-99
75
Y or N
Y