DAYLIFF EXPRESS D1-1ph Installation & Operating Manual page 17

Express electronic pump controller
Table of Contents

Advertisement

Programming Menu
To select the panel operating logic, access the programming menu by pressing the buttons
SETUP , UP and DOWN at the same time on the main screen of the panel.
DESCRIPTION OF PARAMETER
Language
0 ITA / 1 ENG/ 2 FRA / 3 ESP
Operating Logic
Number of Pumps
This parameter enables selection of the number of pumps in the system
(when 1 single pump is selected, the parameter PUMP ROTATION
ENABLED is disabled).
Pump rotation enabled
This parameter enables activation of pump exchange on each demand
from floats or pressure switches. Also, if the main pump thermal cutout
(current overload) trips, the second pump is enabled.
Minimum Level Alarm Output
This parameter enables removal of the minimum level alarm from the
cumulative alarm output.
Type Of Analogue Signal
This parameter enables selection of the type of analogue signal on input
to the panel: 0 = 0-10 V 1 = 4-20 mA
Unit Of Measurement
This parameter enables selection of the measurement unit of the
analogue signal on input to the panel.
Full Scale Of Analogue Signal
This parameter enables selection of the full scale of the analogue signal
on input to the panel.
13
VALUE
FAULT
0
0
4
-
As per order
1-4
Y or N
Y
Y or N
Y
0 or 1
As per order
% + or % -
As per order
m or bar
As per order
1.0 - 999.9

Advertisement

Table of Contents
loading

Table of Contents