DAYLIFF EXPRESS D1-1ph Installation & Operating Manual page 22

Express electronic pump controller
Table of Contents

Advertisement

DESCRIPTION OF PARAMETER
COS-PHI Alarm Output
This parameter enables removal of the dry running alarm from the
cumulative alarm output.
Type Of Analogue Signal
This parameter enables selection of the type of analogue signal on input
to the panel:
0 = 0-10 V
Unit Of Measurement
This parameter enables selection of the measurement unit of the
analogue signal on input to the panel.
Full Scale Of Analogue Signal
This parameter enables selection of the full scale of the analogue signal
on input to the panel.
User Menu
On completion of panel operation programming, enter the setup menu to configure the
various data for motor start-up. To access the user menu, press the button SETUP for 4
seconds in the main screen of the panel.
DESCRIPTION OF PARAMETER
Minimum Voltage
Set by default at -10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Voltage
Set by default at +10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Current P1 / P2 / P3 / P4
This parameter enables entry of the maximum current for each motor.
Enter the maximum current value, increasing it by 10-15% with respect to the
rated motor value.
Modifications to operating limits beyond the parameters stated on the model
data plate will immediately render the warranty null and void.
Minimum COS-Phi P1 / P2 / P3 / P4
This parameter sets the minimum Cos-Phi power factor value for each
motor
Enable operation in manual mode, activate in no-load conditions (dry
running), check the power factor reading (e.g. 0.65) and enter the
minimum power factor, increasing it by approx. 0.05.
Automatic Reset On Dry Running Alarm
In the event of a dry running alarm (minimum power factor) the panel
may attempt to reset automatically, which can be programmable in
minutes.
4 reset times can be set, in which the system automatically restarts after
being blocked; By default these values are set as shown below:
The first reset attempt is performed 5 minutes after the dry running alarm.
The second reset attempt is performed 10 minutes after the alarm.
The third reset attempt is performed 15 minutes after the alarm.
The fourth reset attempt is performed 20 minutes after the alarm.
1 = 4-20 mA
6 18
VALUE
FAULT
Y or N
Y
As per order
0 or 1
% + or % -
As per order
m or bar
1.0 - 999.9
As per order
VALUE
FAULT
207 (230)
-
360 (400)
253 (230)
-
440 (400)
1 - ... A
As per order
0.15-1.00
0.80
1° 5 Min
2° 10 Min
1-240min
3° 20 Min
4° 30 Min

Advertisement

Table of Contents
loading

Table of Contents