Danger: An Isolation breakers or switches for both positive and negative conductors between each
battery string and inverter must be installed for maintenance.
Un disjoncteur d 'isolement ou un commutateur doivent
batterie.
Danger: No short circuit or reserved connection of the battery system's anode and cathode.
Toutes les fiches et prises des câbles d'alimentation doivent être orange à orange et noir à
noir. Sinon, cela causera des blessures.
Caution: Wrong communication cables connection will cause the battery system failure.
Une mauvaise connexion des câbles de communication entraî nera une défaillance du
système de batterie.
Grounding
The PowerCube-H1/H2 modules' grounding is based on metal directly touch
between the module's surface and rack's surface. So it don`t need grounding
cables at all. If uses normal rack, it should remove the paint at the corresponding
grounding point.
La mise à la terre des modules PowerCube-H1/H2 repose sur le contact direct des
métaux entre la surface de module et celle du rack. Il n'est donc pas nécessaire de
mettre les câbles à la terre. Si vous utilisez un rack normal, il est possible d'enlever la
peinture aux positions correspondantes.
Rack Grounding:
If there is a grounding metal frame outside the rack, for example, the metal angle steel frame at the
bottom of the container, the fix hole of the fix frame can be fixed directly with the metal frame of
the container. Then through the grounding of the container to ensure reliable grounding.
The cable shall be copper with yellow-green color.
If want to connect the ground cable, it can be connected to the M8 grounding bolt on the frame
base. Grounding cable must ≥6AWG.
Grounding Bolt
23