Reset Button: Long press this button to restart the battery system.
ADD
ADD Switch is a 6 bit dial switches to manually distribute the communication address of the
battery system. Nether position is OFF, means "0". Upper position is ON, means "1". For BMS, 1st bit
to 5th bit is for address allocation, and the 6th bit dial switch support a 120Ω resistance (Terminal
Resistance).
Start
Start function: press more than 5sec until the buzzer rings, to turn on controller.
Black start function: 30 sec after system turned on and finished self-check process, press and hold
the start button again for more than 5sec, after 'STATUS' lamp becomes green, the relay will close
and output for 10 min.
Fonction de démarrage : appuyez plus de 5 secondes jusqu'à ce que le buzzer sonne, pour
allumer le contrôleur.
Fonction Black start : 30 secondes après la mise sous tension du système et la fin du processus
d'auto-vérification, appuyez à nouveau sur le bouton de démarrage et maintenez-le enfoncé
pendant plus de 5 secondes, après que le voyant « STATUS» devienne vert, le relais se fermera et
sortira pendant 10 minutes.
CAN / RS485
CAN Communication Terminal: (RJ45 port) follow CAN protocol, for communication between
battery system and Inverter.
RS485 Communication Terminal: (RJ45 port) follow Modbus RTU protocol, for communication
between battery system and Inverter.
RS232 Terminal
Console Communication Terminal: (RJ45 port) follow RS232 protocol, for manufacturer or
professional engineer to debug or service.
Link Port 1
Link Port 1 Communication Terminal: (RJ45 port) for communication between
multiple serial battery modules and control module.
Mise sous tension: appuyez et maintenez >= 5 sec
jusqu'à ce que le buzzer sonne
13