WAGO-I/O-SYSTEM 750 XTR
750-614/040-000 Potential Distribution XTR
Pos : 28 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/Leistungskontakte/F eldvers orgung - Ü berschrift 3 @ 6\mod_1256294692864_21.doc x @ 43664 @ 3 @ 1
3.2.2

Power Jumper Contacts/Field Supply

Pos : 29 /Serie 750 ( WAGO-I/O-SYST EM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/Vorsic ht/Vorsic ht: Verletz ungsgefahr durc h sc harfkantige M ess erkontakte! @ 6\mod_1256193279401_21.doc x @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
Pos : 30 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/Leistungskontakte 2 LK (Mess er/F eder) - Einlei tung @ 15\mod_1371721641099_21.doc x @ 123714 @ @ 1
The I/O module 750-614/040-000 has 2 self-cleaning power jumper contacts that
supply and transmit power for the field side. The contacts on the left side of the
I/O module are designed as blade contacts and those on the right side as spring
contacts.
Pos : 31 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/Leistungskontakte 2 LK (Mess er/F eder) - Abbildung, ei nfac he Brei te - Standard @ 15\mod_1367500700037_21.doc x @ 118396 @ @ 1

Figure 3: Power Jumper Contacts

Pos : 32 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/Leistungskontakte 2 LK (Mess er/F eder) - Legende @ 15\mod_1371721352500_21.doc x @ 123710 @ @ 1

Table 4: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
4
Pos : 33 /Serie 750 ( WAGO-I/O-SYST EM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/Achtung/Ac htung: M aximal er Strom Leistungs kontakte 10 A @ 3\mod_1226499143500_21.doc x @ 25029 @ @ 1
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Pos : 34 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Type
Function
Spring contact Potential transmission (U
Spring contact Potential transmission (0 V) for field supply
Blade contact
Potential feed-in (0 V) for field supply
Blade contact
Potential feed-in (U
Device Description
) for field supply
v
) for field supply
v
Version 1.1.0
17
Manual