DMP Panel
12 VDC Aux. Output
+
-
1k
ohm
ADEMCO Panel
12 VDC Aux. Output
+
-
12 VDC BELL +
BELL -
NAPCO Panel
12 VDC Aux. Output
+
-
12 VDC BELL +
2.2k
BELL -
ohm
DSC Panel
12 VDC Aux. Output
+
-
1k
12/24 VDC BELL +
ohm
BELL -
24 VDC Panel
12 VDC Aux. Output
+
-
24 VDC BELL +
4.7k
BELL -
ohm
Digital Monitoring Products
8
Use 18-22 AWG for
power supply
connection
for supervision
Use 18-22 AWG for
power supply
connection
Use 18-22 AWG for
power supply
connection
for supervision
Use 18-22 AWG for
power supply
connection
for supervision
10k ohm
Use 18-22 AWG for
power supply
connection
for supervision if required
Figure 8: Zone 4 Bell Connection
+DC- Z1 Z2 Z3 G +Z4- 01 02 T1 R1 T2 R2
+DC- Z1 Z2 Z3 G +Z4- 01 02 T1 R1 T2 R2
1k ohm
+DC- Z1 Z2 Z3 G +Z4- 01 02 T1 R1 T2 R2
1k ohm
+DC- Z1 Z2 Z3 G +Z4- 01 02 T1 R1 T2 R2
1k ohm
+DC- Z1 Z2 Z3 G +Z4- 01 02 T1 R1 T2 R2
+DC- Z1 Z2 Z3 G +Z4- 01 02 T1 R1 T2 R2
1k ohm
1k ohm
DualCom Programming and Installation Guide
Voltages above 1.4 VDC
are considered Alarm
Voltages above 1.4 VDC
are considered Alarm
Voltages above 1.4 VDC
are considered Alarm
Program Zone 4
DO - Alarm
AO - Alarm
Voltages below 0.7 VDC
are considered Alarm
Voltages above 1.4 VDC
are considered Alarm