Warning! When you connect DO channel with inductive load, we suggest adding
one diode in the circuit to protect the APAX-5060PE module. (Refer to
figure below)
APAX-5060PE Specifications
Relay Output
Channels: 12
Relay Type: Form A (SPST)
Switching Capacity and Lifetime of the Contact (For Resistive Load)
VDE: 30,000 operations (5 A @ 250 VAC, 10 operations/minute at 8 C)
70,000 operations (5 A @ 30 VDC, 10 operations/ minute at 85 C)
UL: 60,000 operations (5 A @ 250 VAC)
100,000 operations (5 A @ 30 VDC)
Mechanism: 20,000,000 operations (no load, 300 operations/minute)
Breakdown Voltage: 500 VAC (50/60 Hz)
Contact Resistance: 30 m (maximum)
Insulation Resistance: 1 G (minimum) at 500 VDC
Operating Time: 10 ms maximum at rated voltage (excluding bounce time)
Release Time: 5 ms maximum at rated voltage (excluding bounce time)
Protection
Isolation: 2,500 VDC (Between channels and backplane bus)
Fail Safe Protection*
* When I/O module lose its communication with controller or coupler, the output chan-
nel will generate a pre-defined value
Environment
Operating Temperature: -20 ~ 70C (when mounted vertically)
Storage Temperature: -40 ~ 85C
Relative Humidity: 5 ~ 95% (non-condensing)
General