Note!
This accuracy information only relates to the operating error, not includ-
ing cold connection CJC error. The CJC error can be eliminated by per-
forming CJC compensation.
Configure Different Range for Each Channel: Yes
Resolution:
Voltage
Range
±50 mV
±100 mV
±250 mV
±500 mV
±1 V
±2.5 V
Current
Range
±20 mA
0 ~ 20 mA
4 ~ 20 mA
Thermocouple
Range
Type J
Type K
Type T
Type E
Type R
Type S
Type B
Sampling Rate: 12 samples/second (total)
CMR @ 50/60 Hz: 90 dB
NMR @ 50/60 Hz: 67 dB
Noise Suppression for Frequency: Hardware Filter (50/60 Hz)
Span Drift: ±25 ppm/ C
Zero Drift: ±6 V/ C
Thermocouple Wire Burn-out Detection: Yes
(When the loop resistance > 1K, it will detect as wire burn-out)
Input Characteristic Curve: According to IEC 61131-2
Common Mode Voltage: up to 200 VDC
Wire Burnout Detection: For 4 ~ 20 mA range and all thermocouple type
Protection
Isolation: 2,500 VDC (Between channels and backplane bus)
APAX-5000 I/O Series User Manual
Resolution
16 bit
16 bit
16 bit
16 bit
16 bit
16 bit
Resolution
15 bit
14 bit
14 bit
Resolution
14 bit
14 bit
15 bit
15 bit
14 bit
14 bit
14 bit
34