Installing the UC Open
2
Using the rotary switches, set the controller address. Set the Tens (10's) switch to the tens digit of the
address, and set the Ones (1's) switch to the ones digit.
EXAMPLE If the controller's address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
0
10's
0
1's
CAUTION The factory default setting is 00 and must be changed to successfully install your UC Open.
Wiring for communications
The UC Open communicates using BACnet on the following types of network segments:
•
MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
•
ARC156 communicating at 156 kbps
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.
Wiring specifications for BACnet MS/TP and ARC156
Cable:
Maximum length:
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
UC Open
Installation and Start-up Guide
22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
2000 feet (610 meters)
6